ESS Rack Modules Low Voltage

Features

Rack Module Series is available as HV and LV. High scalability offers the best flexibility in the market. Up to 2.5MWh of capacity can be reached with parallel or serial connections with the LV or HV hub.

Modules are equipped with WeCo patented balancing systems with fast equalization capability and dynamic balancing capabilities

Rack Modules, either LV or HV, are the most compact modules in the series. They are designed to be used in both domestic and industrial applications. The 5K3 can be used with numerous inverter brands.

5K3 XP Rack HV Module

Module Capacity kWh
5,3
Single Module Nominal Voltage (Vdc)
51,2
Application
High Voltage Application
Modules Expandability
HV Mode: Max 16 Modules in Series with Single HV Box + One HV Cluster Max 10 HV Clusters composed by maximum 16 modules in serial connection each
Voltage Range (Vdc)
47,5 - 58,4 BMS dynamically adjusts the operating values
Capacity (Ah)
105
Usable Capacity (Ah)
100
Dimensions (mm)
550 x 430 x 155
Weight (kg)
57,3
Charge / Discharge Current (A)
100 (150 30sec)
Peak Discharge Current
200 Peak 5 s
Depth of Discharge
Up to 100%
Communication Port
RS485, CAN, 232, Wi-Fi
Modules in Serial Connection
Up to 16 pcs (934Vdc Max String Voltage)
Discharge Temperature (°C)**
-20 ~+60
Charge Temperature (°C)**
-10 ~+55
Shelf Temperature (°C)**
-10 ~+45
Humidity (%)
5 ~ 95
Altitude (m)
< 3000
Design Life
15 Years (25°C)
Expected Life Cycles EOL 80%
> 7000 (25°C)
Standards
IEC62619 UL1973 CE IEC 61000 UN38.3
Features
Auto balancing BMS, 16 channels equalizer, Module local monitoring
Protections
Fuse: 200A / 1000Vdc Four protection logics for HV Box, Real Time Balancing, Adaptive charge/discharge CAN logic, Three step adaptive charging logic, 2xDI/DO programmable ports, Mobile APP for monitoring, control, debugging, firmware update and historical information

*- Module net usable energy is managed by the BMS control logic to 100Ah
**-See Warranty Terms and the Standard Test Conditions ’’STC’’ and the operative temperature
All data subject to the change without prior notice, no part of this document can be copied or reproduced without writtent
permission of WeCo
5K3 –XP Is designed to operate with rack support and indoor

*See terms and conditions

5K3 XP Rack LV Module

Module Capacity kWh
5,3
Single Module Nominal Voltage (Vdc)
51.2
Application
Low Voltage Application
Modules Expandability
LV Mode: Max 15 Modules in Parallel = 1 LV Cluster Max 7 LV Clusters composed by maximum 15 modules in serial connection each + LV HUB
Voltage Range (Vdc)
47,5 - 58,4 BMS dynamically adjusts the operating values
Capacity (Ah)
105
Usable Capacity (Ah)
100
Dimension (mm)
550 x 430 x 155
Weight (kg)
57,3
Charge / Discharge Current (A)
100 (150 30sec)
Peak Discharge Current
200 Peak 5 s
Depth of Discharge
Up to 100%
Communication Port
RS485, CAN, 232, Wi-Fi
Modules in Serial Connection
Up to 15 pcs in parallel
Discharge Temperature (°C)**
-20 ~+60
Charge Temperature (°C)**
-10 ~+55
Shelf Temperature (°C)**
-10 ~+45
Humidity (%)
5 ~ 95
Altitude (m)
< 3000
Design Life
10 Years (25°C)
Expected Life Cycles EOL 80%
> 7000 (25°C)
Standards
IEC62619 UL1973 CE IEC 61000 UN38.3
Features
Auto balancing BMS, 16 channels equalizer, module local monitoring
Protections
Fuse: 150A / 60Vdc Contactor 150A/60Vdc, Real-time balancing, Adaptive charge/discharge CAN logic, Three steps adaptive charging logic, 2xDI/DO programmable ports, Mobile App for monitoring, control, debugging, firmware update and historical information

*- Module net usable energy is managed by the BMS control logic to 100Ah
**-See Warranty Terms and the Standard Test Conditions ’’STC’’ and the operative temperature
All data subject to the change without prior notice, no part of this document can be copied or reproduced without the written
permission of WeCo
5K3 –XP Is designed to operate with rack support and indoor or in IP56 Cabinets

*See terms and conditions

Rack 4K4 LV Module

Single Module

Model 4K4 LV RACK 19”
Rack LB 48-86-Low Voltage
Voltage
Standard 48Vdc
Operative voltage
46.3-57.8Vdc
Voltage – cut out/cut off
44-58.8Vdc
Nominal cluster capacity
86-430 Ah
Cell type
LFP O-Li
Power output peak
5kW
Nominal power
4.5 kW
Expected cycles @ STC
7000
Nominal current Input/Output BMS
86 A
Operative temperature in discharge
-20°C + 60°C
Net Weight
48 kg
Installation mode
Rack 19” 4U ( depth 560mm)
Operational expectation up to:
15 years
Stock period without recharge
2 years from the production date and in the Temp. range of -5°C + 40°C recharge every 4 months
Display
RUN BUTTON + BREAKER *accessory
Accessories
Data cable: CAN , RS 232, RS 485 Earthing cable: Single core yellow/green with ring terminal
Standards
IEC 61600-6-3: 2017 61600-3-2:2014 61000-3-3:2013 61600-6-2007 CE UN 38.3
Enclosure
Steel
Warranty
10 years
IP grade
IP20
*See terms and conditions

Rack 4K4 LV Module

PARALLEL CONFIGURATION

Simply light, heavy-duty application, industry standard.

Easy to expand, Industrial Design, fast connection, standard 19’’ 4U.

N. of Modules
2
3
4
5
6
7
8
Rated Voltage
52,5
Voltage Range
44.8-58.8
Rated Ah
172
258
344
430
516
602
688
Cell Type
LFP Prismatic
Max Cycles Expeted @ STC
7000
Charging Temperature
-10℃/+45℃
Discharging Temperature
-20℃/+60℃
Communication Interface
CAN2.0/RS485/RS232
Max Parallel Units
5 Units without Master BMU
Battery Protection
Over Charging/Over Discharge/Over
Temperature/Over
*See terms and conditions